PREL202102381
Electrical
Closed
VILLA SIENA LLC
Replacement
3022 N Josey Ln Unit #2205 - VILLA SIENA -Outdoor meter and wires were burnt into conduit. Added 100A outdoor disconnect below meter. Made feeder wires between disconnect and indoor panel a 4-wire system. Added ground rods and bare #6 for outdoor disconnect. Made sure to separate the branch circuit grounds and neutral wires in panel and isolated neutral from ground. Ground/Neutral bond is now outside at 1st means of disconnect.