Summary

PRER202206638
Early Release
Permit(s) Issued
KELLER SPRINGS VILLAGE LP
New Construction
2155 Marsh Ln, Suite: 124, Mickey's Day Care Install an underground fire line and tap the city main. We Will: • Excavate Trench for Pipe for the Underground Lead-In • Connect to Existing 10” Underground Main Utilizing a Hot or Wet Tap • A 10” x 8” Tapping Tee or Stainless-Steel Tapping Sleeve Will be Used • Install 8” Tapping Valve • The Tapping Valve is a Non-Rising Stem Gate Valve with a Roadway Box • Install Approximately 38’ of 8” Blue Brute Pipe with No Offsets • Install an 8” Stainless Steel Spigot • PVC Pipe is Blue Brute C-900, DR – Slip Joint • Pour Thrust Blocks • Center Load Pipe • Install Mega Lugs at Fittings • Provide Sand or Gravel Bedding as Required COMPLETING WORK • Pressure Test Work as Required • Back Fill with Dirt Removed • Compact Back Fill in Lifts • Clean Up and Haul Off MATERIALS USED • Underground Pipe to be PVC Blue Brute C-900, DR-14 Slip Joint • Underground Fittings to be Small Body Ductile Iron Mechanical Joint • Restraints to be Mega Lug or Similar • Underground Valves to be Non-Rising Stem Gate Valves • All Material to be UL or FM Approved for Underground Work • 8” Valve • 8” Stainless Steel Spigot
09/12/2022
11/09/2022
12/27/2023

Locations

Permits

Permit Number: PRER202206638-ER1

Early Release
Expired

Conditions

There are no conditions for this permit application, or you are not authorized to view them.