PRFR202208881
Fire
Permit(s) Issued
SANDY LAKE IV LTD
Addition
1725 Sandy Lake Rd, Western Extrusion SCOPE OF WORK IS TO MODIFY EXISTING SPRINKLER SYSTEM TO ACCOMMODATE INSURANCE REQUIREMENTS. NEW DRY SPRINKLER 1725 Sandy Lake Rd, Carrollton, TX 75006 1725 Sandy Lake Rd, Carrollton, TX 75006 SYSTEM TO BE ADDED BELOW CANOPY WITH STORED WOODEN PALLETS. DRY SYSTEM SHALL BE HYDRAULICALLY CALCULATED TO A 0.45 gpm/ft² DENSITY OVER THE ENTIRE AREA. SPRINKLER SYSTEM SHALL OTHERWISE BE INSTALLED PER NFPA 13, 2016. SCOPE OF WORK TO BEGIN AT EXISTING RISER WITH NEW 8" CONNECTION. SYSTEM TO UTILIZE K16.8, STANDARD RESPONSE, 200°F SPRINKLER HEADS. ALL NEW PIPE SHALL BE BLACK STEEL SCHEDULE 10 PIPE. ALL FITTINGS SHALL BE SHORT RADIUS GROOVED FITTINGS. ALL ELECTRICAL MODIFICATIONS TO BE PERFORMED BY OTHERS. FIRE ALARM MODIFICATIONS SHALL BE ATTACHED IN A SEPARATE PACKAGE. ALL PAINTING OF PIPE SHALL BE BY OTHERS. SEALING OF ALL PENETRATIONS SHALL BE BY OTHERS.
12/12/2022
03/01/2023
09/01/2023